QS Model Control panel for diesel generator sets up to 30 KVA equipped with plug, socket and a 4 mt. long multipole wire.Control logic and unit management by electronic microprocessor controller, flush mounted on the panel front side, battery voltage 12V. - Inputs
- measurement of gen-set voltage, frequency (single-phase), mains voltage (single-phase) d.c. voltage generator (dynamo); low oil pressure, high engine temperature, low fuel level and start consent contact, 3 inputs for the remote commands allowing the following operations: switching off of the automatic starts, emergency stop, automatic starting, automatic test (weekly test).
- Outputs
- command of mains contactor, generator contactor, output available on engine starting and running and not available on engine lock, gen-set on and off, start, stop, alarm, battery charger.
By means of the push-buttons on the control panel front side it is possible to enable the manual starting and stopping of the operations, to stop the start function, to set the power pack on automatic operation. The front side of the control panel displays the automatic / manual / test or lock process, if the mains are on, feeding from the mains or the gen-set, regular voltage and frequency of the unit, running motor, kind of failure causing the possible stop (too low oil pressure, engine overheating, low fuel level, broken belt, unit failure, overfrequency, failed start), battery charger on. Q1F Model Control panel for generator sets from 15 to 250 KVA. Control logic by electronic controller, flush-mounted on the panel front side, battery voltage 12 or 24V. - Instruments
- voltmeter, ammeter, frequency meter, hour counter.
- Controls
- programming switch: automatic test, automatic running, locked engine and reset, mains feeding, manual start, feeding from genset; start/stop pushbuttons.
- Signals
- mains available, mains contactor closed, gen-set presence, gen-set contactor closed, battery within nominal value, battery charger on, low fuel level, failed start, cumulative alarm.
- Safety devices
- low oil pressure, high engine temperature, failed start, cumulative damage, emergency stop presetting, generator overload (operating with protection switch), fuel stock.
- Various functions
- single-phase mains sensor, single-phase generator sensor, 4 starting attempts, adjustable gen-set delay, adjustable protection insertion delay, engine cooling delay, mains coming back delay, adjustable stop time, electrovalve/electromagnet stop selection, electronic regulator supply presetting, external emergency stop presetting, automatic test presetting, remote alarm, remote lock, alarm buzzer, automatic battery charger 4A, preheating (only for gen-sets with heater).
- Power section
- 4P mains/generator automatic transfer switch.
- Protection degree
- IP 40 (standard) - IP 54 (on demand).
QM-01 Model AMF panel with automatic transfer switch (ATS) for generating set sets from 8 to 787 KVA. Microprocessor logic, three displays digital instrumentation, programming switch that allows the operation even in case of electronic breakdown, built in automatic 5A battery charger. - Digital parameters:
- mains voltage, generating set voltage, frequency, single-phase current, battery charger voltage and current , total running hours
- Controls:
- programming switch: automatic test, automatic running, locked engine, forced mains supply, manual start, forced generating set supply
Start push button Stop push button enbaled (always on or only in manual start mode) [selectable] Reset / silence push button Two buttons for prameter selection Key combination for led test - Indications and safety devices
- low oil pressure, battery charger dymano, high engine temperature, fuel stock, low wate level, overload, min/max generating set voltage, min/max battery voltage, min/max mains voltage, min/max generating set frequency.
- Power section:
- 4P mains/generating set transfer switch.
- Protection degree:
- IP42.
QM-02 Model AMF panel with automatic transfer switch (ATS) for generating set sets from 8 to 2000 KVA. Microprocessor logic, 2x16 alphanumeric characters display digital instrumentation, progamming switch that allows the oepration even in case of electronic breakdown, built-in automatic 6A battery charger. - Digital parameters:
- mains voltage (three phases), generating set voltage (three phases), generating set frequency, three phases current, voltmeter, kW meter, power factor (cosphi), battery charger current and voltage, oil pressure, engine temperature, fuel level, total running hours, partial running hours, rpm meter, starting attempts meter, failed start attemps, Maintenance in hours, automatic start time test set, automatic stop time set.
- Controls:
- programming switch: automatic test, automatic running, locked engine, manual mains, manual start, ,mains supply from generating set
Start push button Stop push button Fuel pump manual control push button - Indications and safety devices
- Led test on, mains on, mains contactor closed, generating set running, generating set contactors closed, power supply on, cumulative alarm, battery in charge, start, stop, fuel pump control, timer (Prog/Wait), low oil pressure, high water temperature, high oil temperature, low water level, dynamo failure, fuel stock, mains overload, generating set overload, reverse power, min/max voltage, min/max battery voltage, min/max frequency, working hours till maintenance.
- Power section:
- 4P mains/generating set transfer switch.
- Protection degree:
- IP 54.
|